Fox Model 10A Flowmeter Procurement Specification |
|
| |
-
The flowmeter shall operate on the Constant Delta Temperature (Constant Delta T) thermal mass principal. The sensing elements shall consist of two platinum RTD’s. The sensor’s heated element shall operate a constant temperature of 100°F above the gas temperature.
-
The flowmeter shall have a built-in display of flow rate, flow total, and elapse time. The readout shall utilize a LED display consisting of four characters. One 4 to 20mA output will be included.
-
A 4-key keypad will be employed for user programming. Input parameters shall be protected by use of a pin jumper. Nonvolatile memory will retain totalizer and user parameters for up to seven (7) years.
-
The flowmeter shall have a built-in microprocessor allowing field programmability of the 4 mA
setting, 20 mA setting, pipe/duct area and alarm settings.
-
The flowmeter shall measure gas flows over a range of 0 - 32,000 standard feet per minute.
Sensor response time shall be 0.9 seconds for a one (1) Sigma change in velocity.
-
Accuracy shall be ±1.0 percent of reading plus 0.2 percent of full scale and repeatability ±0.2
percent of full scale over an operating temperature range of -40°F to +250°F.
-
All wetted parts are to be 316 SS utilizing an all welded design. Other alloys will optionally be
available.
-
All electronics to be mounted in a single NEMA 4X enclosure. Input power will be 24 VDC.
-
The flowmeter will be FM and CSA approved for for Class I, Division 1, Groups B, C, and D, T3C hazardous locations.
-
The manufacturer shall provide an NIST traceable calibration certificate for the instrument.
-
The Instrument will be the Model 10A manufactured by Fox Thermal Instruments, Inc.,